12kV SSVV (2 Isolator + 2 VCB )CGL RMU Outdoor
    • 12kV SSVV (2 Isolator + 2 VCB )CGL RMU Outdoor

    12KV SSVV (2Isolator + 2VCB ) LUCY RMU Outdoor

    11kV 3 Way CGL MAKE RMU (consist of 2 Isolators & 2 Breaker)11kV 3 Way RMU (consist of 2 Isolators & 2 Breaker)

    • Standalone (integration)
    • Facebook messenger (link)
    • WhatsApp (link)
    • Viber (link)
    • Skype (link)
    • Send an email (link)
    • Telegram (link)
    • Tawk.to (integration)
    • Facebook messenger (integration)
    • Crisp (integration)
    • Tidio (integration)

    11kV 3 Way RMU (consist of 2 Isolators & 2 Breaker)

    a) RING SWITCH / ISOLATOR

    1- 630 Amps. Triple pole, single break, 3-position ('ON', 'OFF' and 'EARTH') Ring Main
    Switches, each with independent manual charged spring mechanism and fully rated earth
    switch

    1- Air insulated cable boxes with gland plate suitable for bottom entry of single run of 3-core
    cable up to 300sq. mm.
    1- Set (3nos) of Cable Bushings
    1- Capacitive Voltage Indicators –LED Display
    1- Mimic diagram on front panel, complete with status indicators (ON-OFF-EARTH)
    1- Set of Right Angle Boots-NON TOUCH PROOF
    1- Each fault Indicator

    b) CIRCUIT BREAKER / VCB
    1- 630 Amps, Triple pole, Vacuum Circuit Breaker, with independent manual charged
    spring mechanism and fully rated earth switch, with provision for earth of the cable. Earthing
    of the outgoing cable is achieved by the use of CB in series with the off- load disconnector
    /selector switch. This enhances the making capacity of the earth switch.

    1- Air insulated cable box with gland plate suitable for bottom entry of single run of 3-core cable
    up to 300sq. mm
    1- Over current & Earth Fault Relay with digital display & Self Powered (Make: CGL, Type: CGI
    14S)
    1- Set of current transformers for protection circuit mounted on Cable bushings / cable box of
    ratio 200-100/1A, 5P10, 2.5VA
    1- Capacitive Voltage Indicators –LED Display
    1- Mimic diagram on front panel, complete with status indicators (ON-OFF-EARTH)
    1- Epoxy Moulded low energy Tripping Coil for tripping the circuit breaker in fault condition
    1- Local 'PULL TO TRIP' mechanism for emergency trip
    1- Set of Right Angle Boots-NON TOUCH PROOF

    c) GENERAL
    The combined unit shall consist of the following:
    1- Set of 630 Amps continuously rated COPPER bus bars
    1- Set of positive standard mechanical interlocks to avoid unsafe operation
    1- Provision for padlocking for Open, Close, Earth position in correct sequence
    1- Manometer for indicating SF6 gas pressure with green & red zone
    1- Set of hooks strong enough to take the load of entire unit while lifting by means of crane
    1- SF6 tank of 3mm stainless steel, robotically welded construction (having degree of protection
    IP67)
    1- Outer Enclosure (cladding) constructed with Galvatite sheets (having degree of protection
    IP54)
    1- External stud for earthing connections
    1- SF6 gas recharging facility
    Jointing Box – As per requirement

    d) PAINT SHADE
    The unit shall be painted in RAL7035 paint shade

    Data sheet

    COUNTRY OF ORIGIN
    INDIA

    Specific References

    New