12kV VVV+M (3 VCB + Metering ) ABB RMU Outdoor
    • 12kV VVV+M (3 VCB + Metering ) ABB RMU Outdoor

    ABB, 12kV VVV+M (3 VCB + Metering) RMU Outdoor

    ABB Make 12kV VVV+M (3 VCB + Metering ) RMU Outdoor & manually operated.

    • Standalone (integration)
    • Facebook messenger (link)
    • WhatsApp (link)
    • Viber (link)
    • Skype (link)
    • Send an email (link)
    • Telegram (link)
    • Tawk.to (integration)
    • Facebook messenger (integration)
    • Crisp (integration)
    • Tidio (integration)

    Item no. 1 Switchgear 1

    SafePlus compact switchgear Outdoor VVV+M Module

    Total number of modules 3 pcs

    STANDARDS AND MECHANICAL DATA

    Metal Enclosed switchgear: IEC 62271-200 General Purpose switches: IEC 60265-1 Disconnectors and Earthing switches: IEC 62271-102 Switch Fuse Comb3nation: IEC 62271-105 Circuit Breakers: IEC 62271-100 Common clauses: IEC 60694 Pressure of SF6 gas: 1.4 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C outdoor Degree of protection: - SF6 tank: IP 67 - Fusecanisters: IP 67 - Front cover: IP 2X - Cable cover: IP 3X - Enclosure IP 54

    Busbars: 240 mm2 Cu Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 Thickness of Stainless Steel Tank: 2.5 / 3.0 mm Colours: - Front cover: RAL 7035 - Side and cable cover: RAL 7035 - Enclosure IS 632


    ELECTRICAL DATA – 12 kV - 28kV-1min Nominal voltage: 11 kV Rated frequency: 50 Hz Rated current busbars: 630 A Rated current cable switch disconnector : 630 A Short time withstand current: - cable switch disconnector with interface C (400-bolt) bushing: 21 kArms 3 sec. - vacuum circuit breaker with interface C (400-bolt) bushing: 21 kArms 3 sec. Rated current for transformer T-off : 200 / 630 A

    Impulse withstand voltage : To earth and between phases: 75 kV Insulation level: - Power frequency 1 min: 28 kV


    A01 V

    SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (Amech.).

    1 SafePlus type V: Vacuum circuit breaker 12kV, 630A 1 Stored energy mech. for Manual operation 1 Self Powered Over Current and Earth Fault protection relay ADR141S 1 Digital Ammeter 1 Cable bushings interface C (400 bolted), 630A 1 Aux. switch for vacuum circuit breaker position 2NO + 2NC 1 Capacitive voltage indication fixed type VPIS 6-12 kV 1 Vacuum circuit breaker tripped signal 1NO 3 Ring core current transformer type 300/1 A, 2.5VA, 5P10 for protection 1 3 Nos Ring core current transformer type 50/1 A, 2.5VA, class 1.0 for metering 1 Manometer

    A02, A03 V

    SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (Amech.).

    1 SafePlus type V: Vacuum circuit breaker 12kV, 630A 1 Stored energy mech. for Manual operation 1 Self Powered Over Current and Earth Fault protection relay ADR141S 1 Digital Ammeter 1 Cable bushings interface C (400 bolted), 630A 1 Aux. switch for vacuum circuit breaker position 2NO + 2NC 1 Capacitive voltage indication fixed type VPIS 6-12 kV 1 Vacuum circuit breaker tripped signal 1NO 3 Ring core current transformer type 300/1 A, 2.5VA, 5P10 for protection 1 3 Nos Ring core current transformer type 50/1 A, 2.5VA, class 1.0 for metering

    A16 M

    SafePlus M is an air insulated metering module.

    1 SafePlus type M: Air insulated metering module 12kV, 630A 1 Potential transformers with HT fuse on primary side and MCB on secondary side for protection Potential Transformer Primary Voltage: 12kV
    1 Secondary Voltage: 110V/rt.3/110V/3V 1 Number of cores: Cl.1, & 3P 1 Burden core 1: 50 VA / 50VA 1 Space Heater with Thermostat Additional equipment delivered separately or mounted in respective panel. 1 Operating handle 1 Auxiliary suplpy for Ammetr or any other equipment in customer scope.

    Data sheet

    RMU RELAY
    SELF POWERED RELAY
    COUNTRY OF ORIGIN
    INDIA
    RMU MANOMETER
    REQUIRED
    RMU ANNUNCIATOR
    NOT REQUIRED
    RMU MULTIFUNCTION METER REQUIREMENT
    NOT REQUIRED IN VCB
    RMU AMMETER REQUIREMENT
    NOT REQUIRED
    RMU SCADA COMPATIBILITY
    NO
    RMU SHORT CIRCUIT FPI WITH CONTACT
    NOT REQUIRED
    RMU SHORT CIRCUIT FPI
    NOT REQUIRED
    RMU EARTH FAULT FPI
    NOT REQUIRED
    RMU CURRENT RATING
    630A
    RMU METERING PT
    WITH ONLY PT
    RMU BATTERY & CHARGER
    NOT REQUIRED
    RMU OPERATION
    MANUAL WITHOUT SCADA CONTACT
    RMU CONFIGURATION
    ONE METERING
    RMU CONFIGURATION
    THREE VCBs
    RMU EXTENSIBILITY
    NON EXTENSIBLE
    RMU APPLICATION
    OUTDOOR IP54
    RMU STC RATING
    21KA FOR 3 SECONDS

    Specific References

    New