ABB, 12kV CCCVV RMU
Outdoor Type, 12kV, 630A, 21kA for 3 Sec, Non-Extensible Outdoor Ring Main Unit Comprising of 3 No. Ring Load Break Switches & 2 No. Vacuum Circuit Breakers
Switchgear :
Outdoor Type, 12kV, 630A, 21kA for 3 Sec, Non-Extensible Outdoor Ring Main Unit Comprising of 3 No. Ring Load Break Switches & 2 No. Vacuum Circuit Breakers
SafePlus compact switchgear : Total number of modules 4 pcs
A01 C
SafePlus C is a cable switch module with a three position load break switch and earthing switch, busbars, interlocking and earthbar.
1 SafePlus type C: Cable switch 12kV, 630A 1 Manometer 1 Snap action mech. for Manual operation 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Earth Fault Indicator 1 Capacitive voltage indication fixed type VPIS 9-15 kV 1 Cable support bars, standard for 1-way unit A02, A03 C
SafePlus C is a cable switch module with a three position load break switch and earthing switch, busbars, interlocking and earthbar.
1 SafePlus type C: Cable switch 12kV, 630A 1 Snap action mech. for Manual operation 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Earth Fault Indicator 1 Capacitive voltage indication fixed type VPIS 9-15 kV 1 Cable support bars, standard for 1-way unit
A 04, 05 V
SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy
1 SafePlus type V: Vacuum circuit breaker 12kV, 630A 1 Stored energy mech. for Manual operation 1 Self Powered Over Current and Earth Fault protection relay ADR141S 1 Cable bushings interface C (400 bolted), 630A 1 Capacitive voltage indication fixed type VPIS 6-12 kV 3 Ring core current transformer type 60/1 A, 2.5VA, 5P10 for protection
Additional equipment delivered separately
1 Operating handle
Data sheet
- RMU VOLTAGE RATING
- 11KV
- RMU CURRENT RATING
- 630A
- RMU STC RATING
- 21KA FOR 3 SECONDS
- RMU APPLICATION
- INDOOR
- RMU EXTENSIBILITY
- NON EXTENSIBLE
- RMU CONFIGURATION
- THREE ISOLATORS
- RMU CONFIGURATION
- TWO VCBs
- RMU OPERATION
- MANUAL WITHOUT SCADA CONTACT
- RMU RELAY
- SELF POWERED RELAY
- COUNTRY OF ORIGIN
- INDIA