22kV SSV(2 Isolators + 1 VCB) Motorized LUCY RMU INDOOR
    • 22kV SSV(2 Isolators + 1 VCB) Motorized LUCY RMU INDOOR

    22kV SSV(2 Isolators + 1 VCB) Motorized LUCY RMU INDOOR

    1. Indoor 22kV SSV(2 Isolators + 1 VCB) Motorized RMU with Touch Proof Termination Kits
    • Standalone (integration)
    • Facebook messenger (link)
    • WhatsApp (link)
    • Viber (link)
    • Skype (link)
    • Send an email (link)
    • Telegram (link)
    • Tawk.to (integration)
    • Facebook messenger (integration)
    • Crisp (integration)
    • Tidio (integration)

    22kV, 630A, 21kA/3sec, SSV Non-Extensible Indoor Motorized type Ring Main Unit

    MCR Type Compact switchgear

    Total number of modules 3 pcs


    STANDARDS AND MECHANICAL DATA

    Metal Enclosed switchgear: IEC 62271-200 General Purpose switches: IEC 60265-1 Disconnectors and Earthing switches: IEC 62271-102 Circuit Breakers: IEC 62271-100 Common clauses: IEC 60694 Pressure of SF6 gas: 1.2 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C Indoor Degree of protection: - SF6 tank: IP 67 - Front cover: IP 2X - Cable cover: IP 3X - Enclosure IP 54 Colours: - Front cover: RAL 7035 - Side and cable cover: IS 632 DA Grey - Enclosure IS 632 DA Grey


    ELECTRICAL DATA – 22 kV - 120kV-1min Nominal voltage: 22 kV Rated frequency: 50 Hz Rated current busbars: 630 A Rated current cable switch disconnector : 630 A Short time withstand current: - cable switch disconnector with interface C (400-bolt) bushing: 20 kArms 3 sec. - vacuum circuit breaker with interface C (400-bolt) bushing: 20 kArms 3 sec. Rated current for transformer T-off : 630 A

    Impulse withstand voltage : To earth and between phases: 120 kV Insulation level: - Power frequency 1 min: 60 kV

    A01, A02 S: On Load Isolator

    C is a cable switch module with a three position load break switch and earthing switch, busbars, interlocking and earthbar.

    1 S – module 1 Manometer (only one per RMU Module) 1 Cable bushing, 630A, bolted 1 Motorized Operating mechanism 1 Earth Fault Indication 1 Capacitive voltage indication fixed type VPIS 1 Cable cover standard with Interlocking



    A03 V: Vacuum Circuit Breaker

    V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism.

    1 V – module 1 Cable bushing 400 series bolted, 630A, bolted 1 Motorized Operating mechanism 1 Capacitive voltage indication fixed type VPIS 1 Self-Powered Protection relay CGL make 3 Protection CT _100-50/1_5P10_for CGL relay 3 100/1A, Class 1.0, 2.5VA CT for metering 1 Cable cover standard with Interlocking



    Additional equipment delivered separately or mounted in respective panel.

    1. Operating handle 2. 22kV Touch Proof Termination Kits 3. Auxiliary supply AC and DC shall be in customers scope for motor / RMU operation

    Data sheet

    RMU VOLTAGE RATING
    22KV
    RMU CURRENT RATING
    630A
    RMU STC RATING
    21KA FOR 3 SECONDS
    RMU APPLICATION
    INDOOR
    RMU CONFIGURATION
    TWO ISOLATORS
    RMU CONFIGURATION
    ONE VCB
    RMU OPERATION
    MOTORISED WITHOUT SCADA CONTACT
    COUNTRY OF ORIGIN
    INDIA

    Specific References

    New