12kV VVV+M (3 VCB + Metering ) ABB RMU Outdoor
  • 12kV VVV+M (3 VCB + Metering ) ABB RMU Outdoor

ABB, 12kV VVV+M (3 VCB + Metering) RMU Outdoor

ABB Make 12kV VVV+M (3 VCB + Metering ) RMU Outdoor & manually operated.

Item no. 1 Switchgear 1

SafePlus compact switchgear Outdoor VVV+M Module

Total number of modules 3 pcs

STANDARDS AND MECHANICAL DATA

Metal Enclosed switchgear: IEC 62271-200 General Purpose switches: IEC 60265-1 Disconnectors and Earthing switches: IEC 62271-102 Switch Fuse Comb3nation: IEC 62271-105 Circuit Breakers: IEC 62271-100 Common clauses: IEC 60694 Pressure of SF6 gas: 1.4 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C outdoor Degree of protection: - SF6 tank: IP 67 - Fusecanisters: IP 67 - Front cover: IP 2X - Cable cover: IP 3X - Enclosure IP 54

Busbars: 240 mm2 Cu Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 Thickness of Stainless Steel Tank: 2.5 / 3.0 mm Colours: - Front cover: RAL 7035 - Side and cable cover: RAL 7035 - Enclosure IS 632


ELECTRICAL DATA – 12 kV - 28kV-1min Nominal voltage: 11 kV Rated frequency: 50 Hz Rated current busbars: 630 A Rated current cable switch disconnector : 630 A Short time withstand current: - cable switch disconnector with interface C (400-bolt) bushing: 21 kArms 3 sec. - vacuum circuit breaker with interface C (400-bolt) bushing: 21 kArms 3 sec. Rated current for transformer T-off : 200 / 630 A

Impulse withstand voltage : To earth and between phases: 75 kV Insulation level: - Power frequency 1 min: 28 kV


A01 V

SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (Amech.).

1 SafePlus type V: Vacuum circuit breaker 12kV, 630A 1 Stored energy mech. for Manual operation 1 Self Powered Over Current and Earth Fault protection relay ADR141S 1 Digital Ammeter 1 Cable bushings interface C (400 bolted), 630A 1 Aux. switch for vacuum circuit breaker position 2NO + 2NC 1 Capacitive voltage indication fixed type VPIS 6-12 kV 1 Vacuum circuit breaker tripped signal 1NO 3 Ring core current transformer type 300/1 A, 2.5VA, 5P10 for protection 1 3 Nos Ring core current transformer type 50/1 A, 2.5VA, class 1.0 for metering 1 Manometer

A02, A03 V

SafePlus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (Amech.).

1 SafePlus type V: Vacuum circuit breaker 12kV, 630A 1 Stored energy mech. for Manual operation 1 Self Powered Over Current and Earth Fault protection relay ADR141S 1 Digital Ammeter 1 Cable bushings interface C (400 bolted), 630A 1 Aux. switch for vacuum circuit breaker position 2NO + 2NC 1 Capacitive voltage indication fixed type VPIS 6-12 kV 1 Vacuum circuit breaker tripped signal 1NO 3 Ring core current transformer type 300/1 A, 2.5VA, 5P10 for protection 1 3 Nos Ring core current transformer type 50/1 A, 2.5VA, class 1.0 for metering

A16 M

SafePlus M is an air insulated metering module.

1 SafePlus type M: Air insulated metering module 12kV, 630A 1 Potential transformers with HT fuse on primary side and MCB on secondary side for protection Potential Transformer Primary Voltage: 12kV
1 Secondary Voltage: 110V/rt.3/110V/3V 1 Number of cores: Cl.1, & 3P 1 Burden core 1: 50 VA / 50VA 1 Space Heater with Thermostat Additional equipment delivered separately or mounted in respective panel. 1 Operating handle 1 Auxiliary suplpy for Ammetr or any other equipment in customer scope.

ডাটা সিট

RMU RELAY
COUNTRY OF ORIGIN
RMU MANOMETER
RMU ANNUNCIATOR
RMU MULTIFUNCTION METER REQUIREMENT
RMU AMMETER REQUIREMENT
RMU SCADA COMPATIBILITY
RMU SHORT CIRCUIT FPI WITH CONTACT
RMU SHORT CIRCUIT FPI
RMU EARTH FAULT FPI
RMU CURRENT RATING
RMU METERING PT
RMU BATTERY & CHARGER
RMU OPERATION
RMU CONFIGURATION
RMU CONFIGURATION
RMU EXTENSIBILITY
RMU APPLICATION
RMU STC RATING