12kV SafeLink CB ABB RMU
  • 12kV SafeLink CB ABB RMU

ABB, 12kV CCV SafeLink CB RMU

12kV SafeLink CB RMU 12kV SafeLink CB RMU ,ABB MAKE

HT Panel Outdoor type (RMU UNIT) :- 1 No. 11KV, 400/630A 21KA/3 Sec outdoor type, Non-extensible Manual Operated SF6 gas insulated Ring Main Unit  with 2Nos. load Switches 1No. Vacuum Circuit breaker enclosed in a stainless steel tank with self powered microprocessor bases numerical relay and dedicated CT’s for protection of Transformer.-

LOAD BREAK SWITCH 1 :

SafeLink CB C is a cable switch module with a three position load break switch and earthing switch, busbars, interlocking and earthbar with Side Cable Termination

1 SafeLink CB type C: Cable switch 12kV, 630A 1 Manometer 1 Snap action mech. for manual operation 1 Cable cover standard with Interlocking 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Capacitive voltage indication fixed type VPIS 9-15 kV 1 Cable support bars, standard for 1-way unit

LOAD BREAK SWITCH 2 :

SafeLink CB C is a cable switch module with a three position load break switch and earthing switch, busbars, interlocking and earthbar. with Side Cable Termination

1 SafeLink CB type C: Cable switch 12kV, 630A 1 Snap action mech. for manual operation 1 Cable cover standard with Interlocking 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Capacitive voltage indication fixed type VPIS 9-15 kV 1 Cable support bars, standard for 1-way unit

VCB 1 :

SafeLink CB V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy with Rear Cable Termination

1 SafeLink CB type V: Vacuum circuit breaker 12kV, 630A 1 Self Powered Over Current and Earth Fault protection relay ADR141S 1 Cable bushings interface C (400 bolted), 630A 1 Capacitive voltage indication fixed type VPIS 6-12 kV 3 Ring core current transformer type 100/1 A, 2.5VA, 5P10 for protection 1 Aux. contacts for VCB & Earth Position 1 Stored energy mech. EL2 for Manual operation

Data sheet

RMU RELAY
SELF POWERED RELAY
COUNTRY OF ORIGIN
INDIA
RMU MANOMETER
REQUIRED
RMU ANNUNCIATOR
NOT REQUIRED
RMU MULTIFUNCTION METER REQUIREMENT
NOT REQUIRED IN VCB
RMU AMMETER REQUIREMENT
NOT REQUIRED
RMU SCADA COMPATIBILITY
NO
RMU SHORT CIRCUIT FPI WITH CONTACT
NOT REQUIRED
RMU SHORT CIRCUIT FPI
NOT REQUIRED
RMU EARTH FAULT FPI
NOT REQUIRED
RMU VOLTAGE RATING
11KV
RMU METERING PT
NO PT REQUIRED
RMU BATTERY & CHARGER
NOT REQUIRED
RMU OPERATION
MANUAL WITHOUT SCADA CONTACT
RMU CONFIGURATION
ONE VCB
RMU CONFIGURATION
TWO ISOLATORS
RMU EXTENSIBILITY
NON EXTENSIBLE
RMU APPLICATION
OUTDOOR IP54
RMU STC RATING
21KA FOR 3 SECONDS
RMU CURRENT RATING
630A

Specific References

New

Download

SAFELINK CB ABB CATALOGUE