L&T, 4 Pole, 100-250A, DN2-250S MCCB
Conforms to IS/IEC 60947-2 & IEC 60947-2
Range: 40A to 1250A, 3P & 4P
Choice of 36kA / 50kA / 70kA breaking capacities
Adjustable Over Load from 0.4 - 1.0 x In
Adjustable Short Circuit from 1.5 - 8 x Ir
Inbuilt Instantaneous Protection
Inbuilt ground fault protection from 20% - 50% of In
Adjustable neutral overload protection available : 50% to 150% of Ir
Provision of Thermal Memory : ON/OFF
Variable trip class at 7.2 Ir & 6 Ir
Front LED indication of Over Load (Ready, Over load pre-alarm & Overload)
Panel mounted display available for Current metering & trip record
Manual, Rotary or Motorised versions available @
For 3 phase 4 wire system, External neutral CTs available for 3P MCCBs
Wide Range of snap fit Internal and External Accessories
Reference
CM92161OOOOAG
Data sheet
MCCB MODEL
COUNTRY OF ORIGIN
MCCB PROTECTION TYPE
MCCB CURRENT RATING
MCCB TRIP UNIT
MCCB/MPCB POLES
MCCB THERMAL/ MAGNETIC RELEASE RANGE
MCCB/MCB BREAKING CAPACITY
Condition
New
16 other products in the same category
800A, DN4-1250N, MICROPROCESSOR RELEASE, D SINE MCCB
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 1 - 10 of In, I = 1 - 12 of In.
Breaking capacity at 415V AC, Ics (Icu) - 100%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution
630A, DN3-630N, MICROPROCESSOR RELEASE, D SINE MCCB
Adjustable Thermal Trip Unit, Ics = 50%
Breaking capacity at 415V AC, Ics (Icu) - 100%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution
Adjustable Thermal Trip unit, Ics = 100%.
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In, Extended front (EF) terminals are supplied as standard in T6 1000A MCCB.
50A, DU 100D, THERMAL MAGNETIC RELEASE, DU MCCB
80A, DNO-100D, THERMAL MAGNETIC RELEASE, D SINE MCCB FOR ISOLATION
250A, DN2-250S, MICROPROCESSOR RELEASE, D SINE MCCB