L&T, 4 Pole, 4000A, MANUAL DRAWOUT, C-POWER ACB

C-POWER Draw-Out ACBs

  • Conforms to IS/IEC 60947-2 & IEC 60947-2
  • Current rating from 800A to 6300A
  • Available in 3 Pole/4 Pole, Manually & Electrically operated, Fixed & Draw-out versions
  • High short time fault withstanding capacity, Icu = Ics = Icw for 1 sec for total selectivity
  • High mechanical and electrical operating life
  • 100% rated neutral pole
  • Protection through Thermal - Magnetic (DN1) & Microprocessor releases (SR18, SR18G,  SR18G+D , SR18Gi+D & SR71)
  • Self diagnostic Microprocessor based Releases with on-load testing through TEST button
  • Inbuilt thermal memory
  • Protection Releases conform to EMI/EMC standards
  • Data communication & Power Management
  • Breaker control through MODBUS protocol

C-POWER Draw-Out ACBs will have inbuilt - 6NO+6NC Aux contact, Safety shutter assembly, Racking handle, Door sealing frame, Push-button cover & Rating Error preventor. Option of horizontal & vertical termination upto 4000A also available. Operation counter for 4000A & above.
EDO version includes 240V AC Shunt trip coil, Closing coil and Motor for electrical charging.

Note: 1 NO Aux contact in manual version & 2NO+2NC in electrical version breakers will be pre-wired with accessories mounted in breaker.
In electrically operated breaker with DN1 release, either earth fault or undervoltage protection can be used.