Features of Digital Loadline MCCB
Conforms to IS/IEC:60947-2
Range: 250A to 630A
Different Current Ratings provide selection option depending on varied load conditions.
Ics = 75% of Icu
Breaking Capacity Icu at 415V = 50kA
Offered in different pole configurations based on system requirement
Built in Ground Fault Protection in Four Pole Version
Microprocessor based release with Adjustable Settings
Electronic MCCB offers close, accurate & reliable protection against overload and short circuit fault
True RMS Sensing
Self Power Released - No external power required for basic functioning of the release
Field Testing Provision - Built in operation to check function which helps in externally testing the release without energising the breaker
Release setting using DIP Switches - Allows accurate setting, ensuring reliable system protection/ co-ordination
Reference
IHLLNFE30250
Data sheet
RATED VOTAGE
COUNTRY OF ORIGIN
MCCB PROTECTION TYPE
MCCB FRAME
MCCB CURRENT RATING
MCCB/MPCB POLES
MCCB/MCB BREAKING CAPACITY
Condition
New
16 other products in the same category
Breaking Capacity at 415V AC, Overload "L" Protection- 0.4-1 x In in steps of 0.04, Inst. Short-circuit "I" Protection- OFF - 1-10 x In, Earth Fault "G" Protection- OFF - 0.2 to 1 x In.
Breaking capacity at 415V AC, Ics (Icu) - 100%, L = 0.40 - 1 of In, S = 1 - 10 of In, I = 1 - 10 of In.
FMU (Thermal Magnetic) Release, Adjustable Overload 80-100%, Fixed short circuit 10In.
25A, DNO-100D, THERMAL MAGNETIC RELEASE, D SINE MCCB FOR ISOLATION
FMU (Thermal Magnetic) Release, Adjustable Overload 80-100%, Fixed short circuit 10In.
Adjustable Thermal Magnetic Trip Unit, Ics = 100% Icu