HAVELLS, 4 Pole wSN, 630A, Loadline DIGITAL MCCB
Features of Digital Loadline MCCB
Conforms to IS/IEC:60947-2
Range: 250A to 630A
Different Current Ratings provide selection option depending on varied load conditions.
Ics = 100% of Icu
Breaking Capacity Icu at 415V = 36kA
Offered in different pole configurations based on system requirement
Built in Ground Fault Protection in Four Pole Version
Microprocessor based release with Adjustable Settings
Electronic MCCB offers close, accurate & reliable protection against overload and short circuit fault
True RMS Sensing
Self Power Released - No external power required for basic functioning of the release
Field Testing Provision - Built in operation to check function which helps in externally testing the release without energising the breaker
Release setting using DIP Switches - Allows accurate setting, ensuring reliable system protection/ co-ordination
Reference
IHLLSEE40630
Data sheet
RATED VOTAGE
TYPE OF NEUTRAL
COUNTRY OF ORIGIN
MCCB PROTECTION TYPE
MCCB FRAME
MCCB CURRENT RATING
MCCB/MPCB POLES
MCCB/MCB BREAKING CAPACITY
Condition
New
16 other products in the same category
ATM (Thermal Magnetic) Release, Adjustable Overload 80-100%, Adjustable Short circuit 5-10 In.
Adjustable Thermal Magnetic Trip Unit, Ics = 100% Icu
Breaking capacity at 415V AC, Ics (Icu) - 100%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
Breaking capacity at 415V AC, Ics (Icu) - 100%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution
Electronic Trip Unit, Ics = 100% Icu.
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In, Extended front (EF) terminals are supplied as standard in T6 1000A MCCB.
Fixed Thermal Trip unit, Ics = 100%.