Legrand, 4 Pole, 500A, DPX³ 630 MCCB
Features of DPX3 MCCB
MCCB with Electronic Sg (LSIg) & Energy Metering Protection Unit
Range: 250A – 1600A
Ics=100%Icu
Two Optimum Frames
Breaking Capacity – 36kA, 50kA, 70kA
Protection against Overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s
Protection against Short Circuits: lsd adjustable from 1.5 to 10 x lr, tsd adjustable from 0 to 0.5s
Inbuilt Instantaneous Protection: Ii – Fixed
Protection against Ground Fault: lg adjustable from 0.2 to 1 In & OFF, tg adjustable from 0.1 to 1s
Option for add on module for Earth Leakage Protection
Adjustable sensitivity: 0.03 - 0.3 - 1 - 3A
Adjustable tripping: 0 - 0.3 - 1 - 3s
Integrated energy metering with accuracy class 2
Measure for currents, voltage, frequency, power, energy and harmonics
Internal Battery with battery measure function
Communication Ready via COMM Port
Logical Selectivity Ready (Zone Selective Interlocking)
In Built USB Port for Software Diagnosis
Switchable Thermal Memory
Suitable for Isolation
DPX3 can also be used as an Automatic Transfer Switch (Source transfer S/W)
Reference
4221 94
Data sheet
MCCB MODEL
DPX³ 630
COUNTRY OF ORIGIN
INDIA
MCCB PROTECTION TYPE
MICROPROCESSOR BASED
MCCB CURRENT RATING
500A
MCCB TRIP UNIT
LSIg
MCCB/MPCB POLES
4 POLE
MCCB/MCB BREAKING CAPACITY
50kA
Condition
New
16 other products in the same category
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In, Extended front (EF) terminals are supplied as standard in T6 1000A MCCB.
FMU (Thermal Magnetic) Release, Adjustable Overload 80-100%, Fixed short circuit 10In.
Adjustable Thermal Trip Unit, Ics = 100%
Breaking Capacity at 415V AC, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
16A, DZ1-160D, THERMAL MAGNETIC RELEASE, D SINE MCCB FOR ISOLATION
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.