Legrand, 3 Pole, 1250A, DPX³ 1600 MCCB
Features of DPX3 MCCB
MCCB with Electronic Sg (LSIg) Protection Unit
Range: 40A – 1600A
Breaking Capacity – 25kA, 36kA, 50kA, 70kA
Ics=100%Icu
Three Optimum Frames
Protection against Overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s
Protection against Short Circuits: lsd adjustable from 1.5 to 10 x lr, tsd adjustable from 0 to 0.5s
Inbuilt Instantaneous Protection: Ii – Fixed
Protection against Ground Fault: lg adjustable from 0.2 to 1 In & OFF, tg adjustable from 0.1 to 1s
Option for In built or add on module for Earth Leakage Protection
Adjustable sensitivity: 0.03 - 0.3 - 1 - 3A
Adjustable tripping: 0 - 0.3 - 1 - 3s
In built Display for Current Metering with high accuracy of class 1
Internal Battery with battery measure function
Communication Ready via COMM Port
Logical Selectivity Ready (Zone Selective Interlocking)
In Built USB Port for Software Diagnosis
Switchable Thermal Memory
Suitable for Isolation
DPX3 can also be used as an Automatic Transfer Switch (Source transfer S/W)
Reference
4224 10
Data sheet
MCCB MODEL
DPX³ 1600
COUNTRY OF ORIGIN
INDIA
MCCB PROTECTION TYPE
MICROPROCESSOR BASED
MCCB CURRENT RATING
1250A
MCCB TRIP UNIT
LSIg
MCCB/MPCB POLES
3 POLE
MCCB/MCB BREAKING CAPACITY
50kA
Condition
New
16 other products in the same category
Fixed Thermal Trip Unit, Ics = 50%
Breaking Capacity at 415V AC, Overload "L" Protection- 0.4-1 x In in steps of 0.04, Inst. Short-circuit "I" Protection- OFF - 1-10 x In, Earth Fault "G" Protection- OFF - 0.2 to 1 x In.
ETM (with in-built Earth fault Protection), Adjustable Overload 40 - 100% , Adjustable shortcircuit 2-12 Ir.
Adjustable Thermal Trip unit, Ics = 100%.