      Features of DPXMCCB

      • MCCB with Electronic Sg (LSIg) Protection Unit
      • Range: 40A – 1600A
      • Breaking Capacity – 25kA, 36kA, 50kA, 70kA
      • Ics=100%Icu
      • Three Optimum Frames
      • Protection against Overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s
      • Protection against Short Circuits: lsd adjustable from 1.5 to 10 x lr, tsd adjustable from 0 to 0.5s
      • Inbuilt Instantaneous Protection: Ii – Fixed
      • Protection against Ground Fault: lg adjustable from 0.2 to 1 In & OFF, tg adjustable from 0.1 to 1s
      • Option for In built or add on module for Earth Leakage Protection
      • Adjustable sensitivity: 0.03 - 0.3 - 1 - 3A
      • Adjustable tripping: 0 - 0.3 - 1 - 3s
      • In built Display for Current Metering with high accuracy of class 1
      • Internal Battery with battery measure function
      • Communication Ready via COMM Port
      • Logical Selectivity Ready (Zone Selective Interlocking)
      • In Built USB Port for Software Diagnosis
      • Switchable Thermal Memory
      • Suitable for Isolation
      • DPX3  can also be used as an Automatic Transfer Switch (Source transfer S/W)
      4205 29

      Data sheet

      MCCB MODEL
      DPX³ 250
      COUNTRY OF ORIGIN
      INDIA
      MCCB PROTECTION TYPE
      MICROPROCESSOR BASED
      MCCB CURRENT RATING
      250A
      MCCB TRIP UNIT
      LSIg
      MCCB/MPCB POLES
      3 POLE
      MCCB/MCB BREAKING CAPACITY
      36kA