Legrand, 3 Pole, 40A, DPX³ 250 MCCB
Features of DPX3 MCCB
MCCB with Electronic Sg (LSIg) Protection Unit
Range: 40A – 1600A
Breaking Capacity – 25kA, 36kA, 50kA, 70kA
Ics=100%Icu
Three Optimum Frames
Protection against Overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s
Protection against Short Circuits: lsd adjustable from 1.5 to 10 x lr, tsd adjustable from 0 to 0.5s
Inbuilt Instantaneous Protection: Ii – Fixed
Protection against Ground Fault: lg adjustable from 0.2 to 1 In & OFF, tg adjustable from 0.1 to 1s
Option for In built or add on module for Earth Leakage Protection
Adjustable sensitivity: 0.03 - 0.3 - 1 - 3A
Adjustable tripping: 0 - 0.3 - 1 - 3s
In built Display for Current Metering with high accuracy of class 1
Internal Battery with battery measure function
Communication Ready via COMM Port
Logical Selectivity Ready (Zone Selective Interlocking)
In Built USB Port for Software Diagnosis
Switchable Thermal Memory
Suitable for Isolation
DPX3 can also be used as an Automatic Transfer Switch (Source transfer S/W)
Reference
4205 22
Data sheet
MCCB MODEL
DPX³ 250
COUNTRY OF ORIGIN
INDIA
MCCB PROTECTION TYPE
MICROPROCESSOR BASED
MCCB CURRENT RATING
40A
MCCB TRIP UNIT
LSIg
MCCB/MPCB POLES
3 POLE
MCCB/MCB BREAKING CAPACITY
36kA
Condition
New
16 other products in the same category
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
320A, DN38-400D, THERMAL MAGNETIC RELEASE, D SINE MCCB
FMU (Thermal Magnetic) Release, Adjustable Overload 80-100%, Fixed short Circuit 10In.
Breaking capacity at 415V AC, Ics (Icu) - 100%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 1 - 10 of In, I = 1 - 12 of In.
Breaking Capacity at 415V AC, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
ATM (Thermal Magnetic) Release, Adjustable Overload 80-100%, Adjustable Short circuit 5-10 In.
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In, Extended front (EF) terminals are supplied as standard in T6 1000A MCCB.
ATM (Thermal Magnetic) Release, Adjustable Overload 80-100%, Adjustable Short circuit 5-10 In.