      Features of DPXMCCB

      • MCCB with Electronic S2 (LSI) Protection Unit
      • Range: 40A – 1600A
      • Breaking Capacity – 25kA, 36kA, 50kA, 70kA
      • Protection against overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s
      • Protection against short circuits: lsd adjustable from 1.5 to 10 x lr, tsd adjustable from 0 to 0.5s
      • Inbuilt Instantaneous Protection: Ii – Fixed 
      • Option for In built or add on module for Earth Leakage Protection
      • Adjustable sensitivity: 0.03 - 0.3 - 1 - 3 A
      • Adjustable tripping: 0 - 0.3 - 1 - 3s 
      • In built Display for Current Metering with accuracy of class 1
      • Internal Battery with battery measure function
      • Communication Ready via COMM Port
      • Logical Selectivity Ready (Zone Selective Interlocking)
      • In Built USB Port for Software Diagnosis
      • Suitable for Isolation
      • DPX3 can also be used as an Automatic Transfer Switch (Source transfer S/W) Ics = 100% Icu
      4220 74

      Data sheet

      MCCB MODEL
      DPX³ 630
      COUNTRY OF ORIGIN
      INDIA
      MCCB PROTECTION TYPE
      MICROPROCESSOR BASED
      MCCB CURRENT RATING
      500A
      MCCB TRIP UNIT
      LSI
      MCCB/MPCB POLES
      4 POLE
      MCCB/MCB BREAKING CAPACITY
      50kA

      Specific References