    Features of DPXMCCB

    • MCCB with Electronic S2 (LSI) Protection Unit
    • Range: 40A – 1600A
    • Breaking Capacity – 25kA, 36kA, 50kA, 70kA
    • Protection against overloads: lr adjustable from 0.4 to 1 x ln, tr adjustable from 3 to 30s
    • Protection against short circuits: lsd adjustable from 1.5 to 10 x lr, tsd adjustable from 0 to 0.5s
    • Inbuilt Instantaneous Protection: Ii – Fixed 
    • Option for In built or add on module for Earth Leakage Protection
    • Adjustable sensitivity: 0.03 - 0.3 - 1 - 3 A
    • Adjustable tripping: 0 - 0.3 - 1 - 3s 
    • In built Display for Current Metering with accuracy of class 1
    • Internal Battery with battery measure function
    • Communication Ready via COMM Port
    • Logical Selectivity Ready (Zone Selective Interlocking)
    • In Built USB Port for Software Diagnosis
    • Suitable for Isolation
    • DPX3 can also be used as an Automatic Transfer Switch (Source transfer S/W) Ics = 100% Icu
    4223 06

    Data sheet

    MCCB MODEL
    DPX³ 1600
    COUNTRY OF ORIGIN
    INDIA
    MCCB PROTECTION TYPE
    MICROPROCESSOR BASED
    MCCB CURRENT RATING
    800A
    MCCB TRIP UNIT
    LSI
    MCCB/MPCB POLES
    4 POLE
    MCCB/MCB BREAKING CAPACITY
    36kA