HAVELLS, 3 Pole, 50A, Loadline MCCB Features of Loadline MCCB
Conforms to IS/IEC:60947-2 Range: 25A to 250A Different Current Ratings provide selection option depending on varied load conditions Ics = 75% of Icu Breaking Capacity Icu at 415V = 25kA Offered in different pole configurations based on system requirement In 4Pwsn Version, Neutral make first & break last for addressing Residual Current in the Circuit Adjustable Thermal & Fixed Magnetic Setting Overload Setting is Adjustable Thermal 70-100% & Short Circuit Setting is minimum 10 times of Rated Current Compact Size & Double Insulation Provision of push to tip button Positive dolly position indication to check the ON/OFF status of the breaker Wide range of accessories available Reference IHLAST0050
Data sheet RATED VOTAGE 415V AC COUNTRY OF ORIGIN INDIA MCCB PROTECTION TYPE THERMAL MAGNETIC BASED MCCB FRAME AS MCCB CURRENT RATING 50A MCCB/MPCB POLES 3 POLE MCCB/MCB BREAKING CAPACITY 25kA Condition New
16 other products in the same category
Breaking Capacity at 415V AC, Overload "L" Protection- 0.4-1 x In in steps of 0.04, Inst. Short-circuit "I" Protection- OFF - 1-10 x In, Earth Fault "G" Protection- OFF - 0.2 to 1 x In.
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
800A, DN4-1250N, MICROPROCESSOR RELEASE, D SINE MCCB
ATM (Thermal Magnetic) Release, Adjustable Overload 80-100%, Adjustable Short circuit 5-10 In.
MGGB with Intelligent Release - N Type
FMU (Thermal Magnetic) Release, Adjustable Overload 80-100%, Fixed short Circuit 10In.