HAVELLS, 4 Pole wSN, 40A, Loadline MCCB Features of Loadline MCCB
Conforms to IS/IEC:60947-2 Range: 25A to 160A Different Current Ratings provide selection option depending on varied load conditions Ics = 75% of Icu Breaking Capacity Icu at 415V = 10kA Offered in different pole configurations based on system requirement Fixed Thermal & Fixed Magnetic Setting Overload Setting is Fixed and Short Circuit Setting is minimum 10 times of Rated Current Compact Size & Double Insulation In 4Pwsn Version, Neutral make first & break last for addressing Residual Current in the Circuit Provision of push to tip button Positive dolly position indication to check the ON/OFF status of the breaker Wide range of accessories available Reference IHLGNF0040
Data sheet RATED VOTAGE 415V AC COUNTRY OF ORIGIN INDIA MCCB PROTECTION TYPE THERMAL MAGNETIC BASED MCCB FRAME GN MCCB CURRENT RATING 40A MCCB/MPCB POLES 4 POLE MCCB/MCB BREAKING CAPACITY 16kA Condition New
16 other products in the same category
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
630A, DN3-630N, MICROPROCESSOR RELEASE, D SINE MCCB
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In, Extended front (EF) terminals are supplied as standard in T6 1000A MCCB.
Breaking capacity at 415V AC, Ics (Icu) - 100%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution
32A, DY 125U, THERMAL MAGNETIC RELEASE, DY MCCB FOR ISOLATION
Breaking capacity at 415V AC, Ics (Icu) - 75%, Adjustable thermal (70-100%of In) and fixed magnetic (10 x In) for power distribution