C&S, 3 Pole, 630A, CSC Seies, WiNbreak MCCB
Features of WiNbreak MCCB - CSC Series
Conforms to IS/IEC 60947-2
Breaking Capacity - 18kA, 26kA, 37kA, 50kA, 65kA & 85kA
FTM (Thermal Magnetic) Release
Wide range of internal & external accessories
Reference
CSC6N3630
Data sheet
MCCB CONTROL VOLTAGE
415V AC
COUNTRY OF ORIGIN
INDIA
MCCB PROTECTION TYPE
THERMAL MAGNETIC BASED
MCCB FRAME
FRAME 5
MCCB CURRENT RATING
630A
MCCB/MPCB POLES
3 POLE
MCCB/MCB BREAKING CAPACITY
37kA
Condition
New
16 other products in the same category
Breaking Capacity at 415V AC, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
MGGB with Intelligent Release - N Type
FMU (Thermal Magnetic) Release, Adjustable Overload 80-100%, Fixed short circuit 10In.
ATM (Thermal Magnetic) Release, Adjustable Overload 80-100%, Adjustable Short circuit 5-10 In.
Fixed Thermal Trip Unit, Ics = 50%
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
Breaking Capacity at 415V AC, Ics (Icu) - 100%, L = 0.4 - 1 of In, S = 0.6 - 10 of In, I = 1.5 - 12 of In, G = 0.2 - 1 of In.
ETM (with in-built Earth fault Protection), Adjustable Overload 40 - 100% , Adjustable shortcircuit 2-12 Ir.
Breaking Capacity at 415V AC, Overload "L" Protection- 0.4-1 x In in steps of 0.04, Inst. Short-circuit "I" Protection- OFF - 1-10 x In, Earth Fault "G" Protection- OFF - 0.2 to 1 x In.